: Sixteen 16-bit high-resolution universal inputs that are auto-selectable for various signal types: Thermistor : 3k (Ibex) or 10k (Type II).
: Native BACnet MS/TP master device communicating over EIA-485 at auto-baud speeds up to 115.2 Kbps.
: Pulse inputs supported on inputs 1–15 (max 100 Hz frequency). vlc 1600 datasheet
: Integrates with intelligent wall sensors like the BACtalk Microset, Microset II, and Microset 4 on input 0 (IN-0) for local data display and setup.
: Operates on 24 VAC @ 50–60 Hz, with a minimum draw of 5 VA. : Sixteen 16-bit high-resolution universal inputs that are
: Fully programmable using Alerton's VisualLogic graphical toolset.
The VLC-1600 is primarily used in central plant systems and lighting panels where high input density is required to monitor multiple process variables simultaneously. It is often paired with other controllers like the VLC-16160-E, which provides the binary outputs the 1600 lacks. hbt-bms-VLC-1600-E-datasheet.pdf : Integrates with intelligent wall sensors like the
According to official documentation from Honeywell Building Automation and Alerton , the device features: